Flexible Power Single Insulated

Home > Products > Building > Flexible Power Single Insulated

ZBD_Black

SINGLE CORE V90HT P.V.C. TO AS/NZS 5000.1

0.6/1KV VOLTAGE RATING

Applications: Power cable 0.6/1KV for fixed applications
Conductor: Nominal 0.2mm bunched flexible Plain Copper Wire to AS1125
Insulation: V90HT PVC to AS3808
Colours: Black, Red, Blue, White, Green/ Yellow
Packs: 100 metres, bulk drum

Typical Properties – Standard: PVC Insulated Unprotected to AS5000.1

Specifications

Code Conductor
No. / Dia
(mm)
Nominal
Area
(mm²)
Insulation
Thickness
(mm)
Electrical
Resistance
at 20°C
(ohm/km)
Nominal
O.D.
(mm)
Mass
(kg/100m)
ZBD112802 128/0.2 4 1.0 4.95 4.8 5.3
ZBD119202 192/0.2 6 1.0 3.3 5.4 7.3
ZBD132202** 322/0.2 10 1.0 1.91 6.3 11.4
ZBD151102** 511/0.2 16 1.0 1.21 7.3 17.1
ZBD179202 784/0.2 25 1.2 0.78 8.8 30
ZBD1112102 1120/0.2 35 1.2 0.554 10.2 37.5
ZBD1159602 1568/0.2 50 1.4 0.386 11.9 51
ZBD1221202 2240/0.2 70 1.4 0.272 14 71.5
ZBD1302102 3040/0.2 95 1.6 0.206 16 97
ZBD1382102 3800/0.2 120 1.6 0.161 17.5 119.1

 

Electrical Data

Code Current
Rating* AMPS
2 Single Cores
Voltage Drop mV/Am at Max operating Temperature –
Single Phase
Voltage Drop mV/Am at Max operating Temperature – 
Three Phase
ZBD112802 40 11.20 9.71
ZBD119202 51 7.50 6.49
ZBD132202 69 4.45 3.86
ZBD151102 92 2.80 2.43
ZBD179202 125 1.78 1.54
ZBD1112102 155 1.29 1.12
ZBD1159602 185 0.96 0.83
ZBD1221202 240 0.62 0.59
ZBD1302102 295 0.51 0.44
ZBD1382102 345 0.41 0.36

* Maximum operating temperature: 75°C in normal Use OR 105°C where not subject to, or protected from, mechanical damage (refer AS/NZS 3008.1.1:2009)
* AMP Ratings are to AS/NZS 3008. Unenclosed-Spaced at 40°C (in air), 25°C (in ground). Refer AS/NZS 3008 for derating factors.
* Tycab holds current independent compliance review report on PVC Cable compliance for GREEN STAR PVC Credit
** TUV AUTHORISED MARKING: TUV022087EA

Colours