Flexible Power Single Core 0.6/1KV Double Insulated

Home > Products > Power & Welding > Flexible Power Single Core 0.6/1KV Double Insulated

ZDU_Orange

SINGLE CORE DOUBLE INSULATED V90HT P.V.C. TO AS/NZS 5000.1

Applications: For fixed power applications
Power: Switchboards, busbars, transformers
Welding: Earth and electrode leads
Automotive: Jumper Leads, Battery chargers
Conductor: Flexible Class 6 Bunched OXYGEN FREE Plain Copper Wire to AS/NZS 1125
Insulation: RoHS Compliant Nitrile (NBR) Modified P.V.C. type V90HT to AS/NZS 3808
Insulation Colour: White
Sheath: RoHS Compliant Nitrile (NBR) Modified P.V.C. type V90HT to AS/NZS 3808
Sheath Colours: Orange – other colours available by request (E.g. Black, Blue, Red)
Packs: 50, 100 metres – other packs by request
Min. Bend Radius: During Installation: 6D – Fixed or Location: 4D

 

Specifications

Code Conductor
No. / Dia
(mm)
Nominal
Area
(mm²)
Insulation
Thickness
(mm)
Sheath
Thickness
(mm)
Electrical
Resistance
at 20°C
(ohm/km)
Nominal
O.D.
(mm)
Mass
(kg/100m)
Typical Properties
STANDARD: V90HT AS/NZS 5000.1, AS/NZS 1995
ZDU132202** 322/0.2 10 1.0 1.4 1.91 9.1 14.42
ZDU151102** 511/0.2 16 1.0 1.4 1.21 10.1 20.16
ZDU179202 784/0.2 25 1.2 1.4 0.78 11.8 29.14
ZDU1112102 1120/0.2 35 1.2 1.4 0.554 13.1 38.96
ZDU1159602 1568/0.2 50 1.4 1.4 0.386 14.9 52.84
ZDU1221202 2240/0.2 70 1.4 1.5 0.272 17 72.34
ZDU1302102 3040/0.2 95 1.6 1.5 0.206 19.3 96.18
ZDU1382102 3800/0.2 120 1.6 1.6 0.161 20.8 117.86

 

Electrical Data

Code Current
Rating* AMPS
2 Single Cores
Voltage Drop mV/Am at Max operating Temperature –
Single Phase
Voltage Drop mV/Am at Max operating Temperature – 
Three Phase
ZDU132202** 69 4.45 3.86
ZDU151102 91 2.80 2.43
ZDU179202 125 1.78 1.54
ZDU1112102 155 1.29 1.12
ZDU1159602 185 0.96 0.83
ZDU1221202 240 0.62 0.59
ZDU1302102 295 0.51 0.44
ZDU1382102 345 0.41 0.36

NOTE:
* Maximum operating temperature: 75°C in normal Use OR 105°C where not subject to, or protected from, mechanical damage (refer AS/NZS 3008.1.1:2009)
* AMP Ratings are to AS/NZS 3008. Unenclosed-Spaced at 40°C (in air), 25°C (in ground). Refer AS/NZS 3008 for derating factors – For Welding AMP Ratings refer to AS/NZS 1995.
* Tycab holds current independent compliance review report on PVC Cable compliance for GREEN STAR PVC Credit
** TUV AUTHORISED MARKING: TUV022088EA

Colours