- General
- Specifications
SINGLE CORE FLEXIBLE
250/440 VOLT
Applications: | Wiring of Communication, Electronic Equipment and Switchboards |
Conductor: | Tinned Copper Wire (TCW) to AS/NZS 1125 |
Insulation: | RoHS Compliant V90HT (105) P.V.C. to AS/NZS 3808 |
Colours: | Black, Blue, Brown, Green / Yellow, Grey, Orange, Pink, Red, Violet, White, Yellow |
Packs: | 100, 1000 metres – other packs by request |
Specifications
Code | Conductor No. / Dia (mm) |
Nominal Area (mm²) |
Insulation Thickness (mm) |
AMP Rating |
Electrical Resistance at 20°C (ohm/km) |
Nominal O.D. (mm) |
Mass (kg/100m) |
|
---|---|---|---|---|---|---|---|---|
FVT11602 | 16/0.20 | 0.5 | 0.6 | 10 | 40.1 | 2.2 | 0.9 | |
FVT12402 | 24/0.20 | 0.75 | 0.6 | 12 | 26.7 | 2.4 | 1.2 | |
FVT13202 | 32/0.20 | 1 | 0.6 | 17 | 20 | 2.6 | 1.5 |
Where used as Fixed Wiring, AMP ratings to AS/NZS 3008.1.1:2009 Table 4 Unenclosed-Spaced 40°C (in air), 25°C (in ground). Refer AS/NZS 3008 for derating factors.
Maximum operating temperature: 75°C in normal use OR 105°C where not subject to, or is protected from, mechanical damage (refer AS/NZS 3008.1.1:2009 Table 1 Clause 3).